LEONARD THS-25 THERMOSTATIC HOSE STATION
ITEM: | PROBLEM: | PARTS REQUIRED:: |
PACKINGS & GASKETS | 1. Leak at handle or cover. 2. Leak between valve cover and base. | 5236, 538 |
PORT SLEEVE ASSEMBLY | 3. Valve delivers either all hot or all cold water, or will not mix consistently. | TG-1/30/ST OR KIT R/THS/N REBUILDING KIT |
THERMOSTAT GROUP | 4. After cleaning or replacing port sleeve assembly, valve will not hold temperature. | TGM-2/50 OR KIT R/THS/N REBUILDING KIT |
CHECKSTOPS, STOPS | 5. Steam bypass into cold supply 6. Cold water bypass into steam supply. | M-20-6E (4 each) 20-65-M (2 each) 30-65-N (2 each) |
Refer to the Operational and Maintenance guide for full Troubleshooting Instructions.
Subcategories in LEONARD THS-25 THERMOSTATIC HOSE STATION
Items in LEONARD THS-25 THERMOSTATIC HOSE STATION